Siemens KNX IP Viewer N 151
Siemens KNX IP Viewer N 151 - web based configuration, 40 functions provided supply up to 80 communication objects for connecting to group address, DIN rail mounted device - 5WG1 151-1AB01
| | Siemens IP Viewer N 151 Features |
 | N151 IP Viewer incorporates a web server for operating and monitoring KNX/KNX systems. |
 | It can display up to 5 operating pages via a standard browser. On this are provided to 40 functions. |
 | A web configuration page allows you to edit the display in a number of languages. |
 | It provides an interface to KNX installations via data networks using the Internet protocol (IP). At the same time, this device provides communication from KNX devices with PCs or other data processing devices (KNXnet/IP Tunnelling). Client software products, such as ETS 3, which are based on the KNXnet/IP tunnel protocol can set up connections to the N151 IP Viewer. |
 | Communication with a visualization software over an IP network (object server connection) is possible (see supported applications). |
| | Technical details |
 | Network communication:- Ethernet: 1OBaseT (10 Mbit/s) - Supported Internet protocols: ARP, ICMP, IGMP, UDP/IP, DHCP - KNXnet/IP to Konnex System Specification: Core, Tunnelling, Device Management |
 | Rated voltage:- Bus: 24V DC (21...3ov DC) - Auxiliary power supply: 24V AC/DC (12... 30V AC/DC) |
 | Power supply:- Bus voltage: via KNX bus line - Operating voltage: from an external SELV power supply AC/DC 24V nominal, permissible input voltage range: AC/DC 12...30V - Recommended power supplies: - before choke voltage from N123 (1 20v AC operating voltage) and N125/21 KNX power supplies -- door bell transformer 4AC3 108, 230V AC/AC 2x12 V (primary/ secondary), 2x0, 33A, width 2SU -- door bell transformer 4AC3 116, 230V AC/AC 2x12 V (primary/ secondary), 2x0, 67A, width 2SU -- door bell transformer 4AC3 140, 230V AC/AC 2x12 V (primary/secondary), 2x1,67A, width 3SU |
 | 1 learning button: to change between normal and addressing modes |
 | Display elements:- 1 yellow LED: Ethernet link signal present (LK) - 1 yellow LED: data traffic on Ethernet (LA) - 1 red LED: for checking bus voltage and to indicate normal mode (LED = Off)/addressing mode (LED = On) |
| | Package |
Unit | 1 |
Back Box | |
Fixing | Din Rail |
Warranty | 12 Months |
VAT | UK VAT @ 17.5% will be added to the total price at Checkout |
Delivery Time | Stock Item |
UK Delivery | Free UK Delivery on orders over £250.00 |